Module: LargeOfficeDetailed
- Defined in:
- lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb
Overview
Custom changes for the LargeOffice prototype. These are changes that are inconsistent with other prototype building types.
AirTerminalSingleDuctVAVReheat collapse
- 
  
    
      #air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    Set the initial minimum damper position based on OA rate of the space and the template. 
Instance Method Summary collapse
- 
  
    
      #model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    geometry adjustments specific to the prototype model. 
- 
  
    
      #model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    hvac adjustments specific to the prototype model. 
- 
  
    
      #model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    swh adjustments specific to the prototype model. 
- 
  
    
      #remove_basement_infiltration(model)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    remove basement infiltration. 
- 
  
    
      #update_waterheater_loss_coefficient(model)  ⇒ Boolean 
    
    
  
  
  
  
  
  
  
  
  
    update water heater loss coefficient. 
Instance Method Details
#air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area) ⇒ Boolean
Set the initial minimum damper position based on OA rate of the space and the template. Zones with low OA per area get lower initial guesses. Final position will be adjusted upward as necessary by Standards.AirLoopHVAC.apply_minimum_vav_damper_positions
| 153 154 155 156 157 158 159 160 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 153 def air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area) min_damper_position = template == '90.1-2010' || template == '90.1-2013' || template == '90.1-2016' || template == '90.1-2019' ? 0.2 : 0.3 # Set the minimum flow fraction air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position) return true end | 
#model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input) ⇒ Boolean
geometry adjustments specific to the prototype model
| 139 140 141 142 143 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 139 def model_custom_geometry_tweaks(model, building_type, climate_zone, prototype_input) # Set original building North axis OpenstudioStandards::Geometry.model_set_building_north_axis(model, 0.0) return true end | 
#model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input) ⇒ Boolean
hvac adjustments specific to the prototype model
| 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 11 def model_custom_hvac_tweaks(model, building_type, climate_zone, prototype_input) system_to_space_map = define_hvac_system_map(building_type, climate_zone) system_to_space_map.each do |system| # find all zones associated with these spaces thermal_zones = [] system['space_names'].each do |space_name| space = model.getSpaceByName(space_name) if space.empty? OpenStudio.logFree(OpenStudio::Error, 'openstudio.model.Model', "No space called #{space_name} was found in the model") return false end space = space.get zone = space.thermalZone if zone.empty? OpenStudio.logFree(OpenStudio::Error, 'openstudio.model.Model', "No thermal zone was created for the space called #{space_name}") return false end thermal_zones << zone.get end return_plenum = nil unless system['return_plenum'].nil? return_plenum_space = model.getSpaceByName(system['return_plenum']) if return_plenum_space.empty? OpenStudio.logFree(OpenStudio::Error, 'openstudio.model.Model', "No space called #{system['return_plenum']} was found in the model") return false end return_plenum_space = return_plenum_space.get return_plenum = return_plenum_space.thermalZone if return_plenum.empty? OpenStudio.logFree(OpenStudio::Error, 'openstudio.model.Model', "No thermal zone was created for the space called #{system['return_plenum']}") return false end return_plenum = return_plenum.get end end # replace EvaporativeFluidCoolerSingleSpeed with CoolingTowerTwoSpeed model.getPlantLoops.each do |plant_loop| next unless plant_loop.name.to_s.include? 'Heat Pump Loop' sup_wtr_high_temp_f = 65.0 sup_wtr_low_temp_f = 41.0 sup_wtr_high_temp_c = OpenStudio.convert(sup_wtr_high_temp_f, 'F', 'C').get sup_wtr_low_temp_c = OpenStudio.convert(sup_wtr_low_temp_f, 'F', 'C').get hp_high_temp_sch = OpenstudioStandards::Schedules.create_constant_schedule_ruleset(model, sup_wtr_high_temp_c, name: "#{plant_loop.name} High Temp - #{sup_wtr_high_temp_f.round(0)}F", schedule_type_limit: 'Temperature') hp_low_temp_sch = OpenstudioStandards::Schedules.create_constant_schedule_ruleset(model, sup_wtr_low_temp_c, name: "#{plant_loop.name} Low Temp - #{sup_wtr_low_temp_f.round(0)}F", schedule_type_limit: 'Temperature') # add cooling tower object cooling_tower = OpenStudio::Model::CoolingTowerTwoSpeed.new(model) cooling_tower.setName("#{plant_loop.name} Central Tower") plant_loop.addSupplyBranchForComponent(cooling_tower) #### Add SPM Scheduled Dual Setpoint to outlet of Fluid Cooler so correct Plant Operation Scheme is generated cooling_tower_stpt_manager = OpenStudio::Model::SetpointManagerScheduledDualSetpoint.new(model) cooling_tower_stpt_manager.setName("#{plant_loop.name} Fluid Cooler Scheduled Dual Setpoint") cooling_tower_stpt_manager.setHighSetpointSchedule(hp_high_temp_sch) cooling_tower_stpt_manager.setLowSetpointSchedule(hp_low_temp_sch) cooling_tower_stpt_manager.addToNode(cooling_tower.outletModelObject.get.to_Node.get) # remove EvaporativeFluidCoolerSingleSpeed object model.getEvaporativeFluidCoolerSingleSpeeds.each do |fluid_cooler| if fluid_cooler.plantLoop.get.name.to_s == plant_loop.name.to_s fluid_cooler.remove break end end end remove_basement_infiltration(model) return true end | 
#model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) ⇒ Boolean
swh adjustments specific to the prototype model
| 127 128 129 130 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 127 def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) update_waterheater_loss_coefficient(model) return true end | 
#remove_basement_infiltration(model) ⇒ Boolean
remove basement infiltration
| 95 96 97 98 99 100 101 102 103 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 95 def remove_basement_infiltration(model) space_infltrations = model.getSpaceInfiltrationDesignFlowRates space_infltrations.each do |space_inf| if space_inf.name.to_s.include? 'Basement' space_inf = nil end end return true end | 
#update_waterheater_loss_coefficient(model) ⇒ Boolean
update water heater loss coefficient
| 109 110 111 112 113 114 115 116 117 118 | # File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb', line 109 def update_waterheater_loss_coefficient(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', '90.1-2016', '90.1-2019', 'NECB2011' model.getWaterHeaterMixeds.sort.each do |water_heater| water_heater.setOffCycleLossCoefficienttoAmbientTemperature(11.25413987) water_heater.setOnCycleLossCoefficienttoAmbientTemperature(11.25413987) end end return true end |